ASHRAE Journal - August 2008 - (Page 65) with the drapes open, and the room full, and everything on. And, you know that someone in some bureaucracy somewhere wants way too much outside air. Therefore, most of the time your latent load dwarfs your sensible load. So, what do you do? You reduce the amount of outside air by installing timers on exhaust fans, and you ignore the faceless bureaucrat. Then, you only run the through-wall unit to control the temperature (i.e., make it the sensible system) and install a dehumidifier in each unit to control the humidity (the latent system) (Photo 6). It’s a primitive, but effective fix. In new designs we hide the dehumidifier better, or better still, we make it part of the ventilation system. Guess where this technology is making an impact? Condos and apartments. Small houses are next. We are already separating the latent from the sensible on most commercial design. After all, it is the sensible thing to do. North Versus South So, why is it worse in the south than the north? In the north, it still gets cold and the outside cold air is pretty dry—and walls tend to dry to the outside in the north—so the size of the moisture drying sink has not changed. But, in the south, walls also dry to the inside. And, if the inside is humid because of the part-load problem, the walls stay wetter because the moisture drying sink is smaller. Additionally, in the south the moisture drive from the exterior into the wall is greater, while at the same time the moisture drive from the wall into the interior is smaller as compared to the corresponding drives in opposite directions in the north. Let me translate. It is easier to get wet from the outside in the south than it is from the inside in the north. It is also easier to dry to the outside in the north than it is to dry to the inside in the south. With less energy available, it gets worse in the south faster than in the north. Good air-conditioning design leads to dry interiors and dry interiors allow walls to dry to the inside. Part-load humidity problems lead to wetter walls. Higher levels of thermal insulation and lower heat gain lead to part-load humidity problems. Not good. Now What? OK, everybody relax. We want and we need much higher levels of thermal control (airtight, insulated assemblies) everywhere. We just have to be smart about it. We want and need ultraefficient glazing, lights, appliances, and reflective surfaces everywhere. We just have to be smart about it. And, we want and need the right amount of outside air whenever we need it. We just have to be smart about it. This is neither expensive nor difficult. It’s just different. We need to modify our building enclosure and mechanical system paradigms. Get used to it or be steamrolled by the change. Insulate on the outside. Back-ventilate and drain your cladding. Separate your sensible load from your latent load. Don’t overventilate. Existing buildings are going to be a bear. And, have a nice day. August 2008 Photo 6: Hotel Room Fix. The through-wall unit controls the temperature (the sensible system). The dehumidifier controls the humidity (the latent system). Joseph W. Lstiburek, Ph.D., P.Eng., is a principal of Building Science Corporation, in Somerville, Mass. Visit www. buildingscience.com. www.info.hotims.com/16017-5 ASHRAE Journal 65 http://www.buildingscience.com http://www.buildingscience.com http://www.ajmfg.com http://www.ajmfg.com http://www.info.hotims.com/16017-5
Table of Contents Feed for the Digital Edition of ASHRAE Journal - August 2008 ASHRAE Journal - August 2008 Contents Commentary Industry News Letters Meetings and Shows Maintain to Sustain—Delivering ASHRAE’s Sustainability Promise Ultraviolet Germicidal Irradiation: Current Best Practices Improving Humidity Control With Energy Recovery Ventilation Single- or Two-Stage Compression Data Center Cooling: Using Wet-Bulb Economizers Building Sciences InfoCenter Practical Pointers Products Emerging Technologies Washington Report People Special Products Classified Advertising Advertising Index ASHRAE Journal - August 2008 ASHRAE Journal - August 2008 - ASHRAE Journal - August 2008 (Page Cover1) ASHRAE Journal - August 2008 - ASHRAE Journal - August 2008 (Page Cover2) ASHRAE Journal - August 2008 - ASHRAE Journal - August 2008 (Page 1) ASHRAE Journal - August 2008 - ASHRAE Journal - August 2008 (Page 2) ASHRAE Journal - August 2008 - Contents (Page 3) ASHRAE Journal - August 2008 - Contents (Page 4) ASHRAE Journal - August 2008 - Commentary (Page 5) ASHRAE Journal - August 2008 - Industry News (Page 6) ASHRAE Journal - August 2008 - Industry News (Page 7) ASHRAE Journal - August 2008 - Industry News (Page 8) ASHRAE Journal - August 2008 - Industry News (Page 9) ASHRAE Journal - August 2008 - Industry News (Page 10) ASHRAE Journal - August 2008 - Industry News (Page 11) ASHRAE Journal - August 2008 - Industry News (Page 12) ASHRAE Journal - August 2008 - Industry News (Page 13) ASHRAE Journal - August 2008 - Industry News (Page 14) ASHRAE Journal - August 2008 - Industry News (Page 15) ASHRAE Journal - August 2008 - Industry News (Page 16) ASHRAE Journal - August 2008 - Industry News (Page BA1) ASHRAE Journal - August 2008 - Industry News (Page BA2) ASHRAE Journal - August 2008 - Letters (Page 17) ASHRAE Journal - August 2008 - Meetings and Shows (Page 18) ASHRAE Journal - August 2008 - Meetings and Shows (Page 19) ASHRAE Journal - August 2008 - Maintain to Sustain—Delivering ASHRAE’s Sustainability Promise (Page 20) ASHRAE Journal - August 2008 - Maintain to Sustain—Delivering ASHRAE’s Sustainability Promise (Page 21) ASHRAE Journal - August 2008 - Maintain to Sustain—Delivering ASHRAE’s Sustainability Promise (Page 22) ASHRAE Journal - August 2008 - Maintain to Sustain—Delivering ASHRAE’s Sustainability Promise (Page 23) ASHRAE Journal - August 2008 - Maintain to Sustain—Delivering ASHRAE’s Sustainability Promise (Page 24) ASHRAE Journal - August 2008 - Maintain to Sustain—Delivering ASHRAE’s Sustainability Promise (Page 25) ASHRAE Journal - August 2008 - Maintain to Sustain—Delivering ASHRAE’s Sustainability Promise (Page 26) ASHRAE Journal - August 2008 - Maintain to Sustain—Delivering ASHRAE’s Sustainability Promise (Page 27) ASHRAE Journal - August 2008 - Ultraviolet Germicidal Irradiation: Current Best Practices (Page 28) ASHRAE Journal - August 2008 - Ultraviolet Germicidal Irradiation: Current Best Practices (Page 29) ASHRAE Journal - August 2008 - Ultraviolet Germicidal Irradiation: Current Best Practices (Page 30) ASHRAE Journal - August 2008 - Ultraviolet Germicidal Irradiation: Current Best Practices (Page 31) ASHRAE Journal - August 2008 - Ultraviolet Germicidal Irradiation: Current Best Practices (Page 32) ASHRAE Journal - August 2008 - Ultraviolet Germicidal Irradiation: Current Best Practices (Page 33) ASHRAE Journal - August 2008 - Ultraviolet Germicidal Irradiation: Current Best Practices (Page 34) ASHRAE Journal - August 2008 - Ultraviolet Germicidal Irradiation: Current Best Practices (Page 35) ASHRAE Journal - August 2008 - Ultraviolet Germicidal Irradiation: Current Best Practices (Page 36) ASHRAE Journal - August 2008 - Ultraviolet Germicidal Irradiation: Current Best Practices (Page 37) ASHRAE Journal - August 2008 - Improving Humidity Control With Energy Recovery Ventilation (Page 38) ASHRAE Journal - August 2008 - Improving Humidity Control With Energy Recovery Ventilation (Page 39) ASHRAE Journal - August 2008 - Improving Humidity Control With Energy Recovery Ventilation (Page 40) ASHRAE Journal - August 2008 - Improving Humidity Control With Energy Recovery Ventilation (Page 41) ASHRAE Journal - August 2008 - Improving Humidity Control With Energy Recovery Ventilation (Page 42) ASHRAE Journal - August 2008 - Improving Humidity Control With Energy Recovery Ventilation (Page 43) ASHRAE Journal - August 2008 - Improving Humidity Control With Energy Recovery Ventilation (Page 44) ASHRAE Journal - August 2008 - Improving Humidity Control With Energy Recovery Ventilation (Page 45) ASHRAE Journal - August 2008 - Single- or Two-Stage Compression (Page 46) ASHRAE Journal - August 2008 - Single- or Two-Stage Compression (Page 47) ASHRAE Journal - August 2008 - Single- or Two-Stage Compression (Page 48) ASHRAE Journal - August 2008 - Single- or Two-Stage Compression (Page 49) ASHRAE Journal - August 2008 - Single- or Two-Stage Compression (Page 50) ASHRAE Journal - August 2008 - Single- or Two-Stage Compression (Page 51) ASHRAE Journal - August 2008 - Data Center Cooling: Using Wet-Bulb Economizers (Page 52) ASHRAE Journal - August 2008 - Data Center Cooling: Using Wet-Bulb Economizers (Page 53) ASHRAE Journal - August 2008 - Data Center Cooling: Using Wet-Bulb Economizers (Page 54) ASHRAE Journal - August 2008 - Data Center Cooling: Using Wet-Bulb Economizers (Page 55) ASHRAE Journal - August 2008 - Data Center Cooling: Using Wet-Bulb Economizers (Page 56) ASHRAE Journal - August 2008 - Data Center Cooling: Using Wet-Bulb Economizers (Page ACP1) ASHRAE Journal - August 2008 - Data Center Cooling: Using Wet-Bulb Economizers (Page ACP2) ASHRAE Journal - August 2008 - Data Center Cooling: Using Wet-Bulb Economizers (Page ACP3) ASHRAE Journal - August 2008 - Data Center Cooling: Using Wet-Bulb Economizers (Page ACP4) ASHRAE Journal - August 2008 - Data Center Cooling: Using Wet-Bulb Economizers (Page ACP5) ASHRAE Journal - August 2008 - Data Center Cooling: Using Wet-Bulb Economizers (Page ACP6) ASHRAE Journal - August 2008 - Data Center Cooling: Using Wet-Bulb Economizers (Page 57) ASHRAE Journal - August 2008 - Data Center Cooling: Using Wet-Bulb Economizers (Page 58) ASHRAE Journal - August 2008 - Data Center Cooling: Using Wet-Bulb Economizers (Page 59) ASHRAE Journal - August 2008 - Building Sciences (Page 60) ASHRAE Journal - August 2008 - Building Sciences (Page 61) ASHRAE Journal - August 2008 - Building Sciences (Page 62) ASHRAE Journal - August 2008 - Building Sciences (Page 63) ASHRAE Journal - August 2008 - Building Sciences (Page 64) ASHRAE Journal - August 2008 - Building Sciences (Page 65) ASHRAE Journal - August 2008 - InfoCenter (Page 66) ASHRAE Journal - August 2008 - InfoCenter (Page 67) ASHRAE Journal - August 2008 - InfoCenter (Page 68) ASHRAE Journal - August 2008 - InfoCenter (Page 69) ASHRAE Journal - August 2008 - InfoCenter (Page 70) ASHRAE Journal - August 2008 - InfoCenter (Page 71) ASHRAE Journal - August 2008 - Practical Pointers (Page 72) ASHRAE Journal - August 2008 - Practical Pointers (Page 73) ASHRAE Journal - August 2008 - Products (Page 74) ASHRAE Journal - August 2008 - Products (Page 75) ASHRAE Journal - August 2008 - Emerging Technologies (Page 76) ASHRAE Journal - August 2008 - Emerging Technologies (Page 77) ASHRAE Journal - August 2008 - Emerging Technologies (Page 78) ASHRAE Journal - August 2008 - Emerging Technologies (Page 79) ASHRAE Journal - August 2008 - Washington Report (Page 80) ASHRAE Journal - August 2008 - People (Page 81) ASHRAE Journal - August 2008 - Special Products (Page 82) ASHRAE Journal - August 2008 - Special Products (Page 83) ASHRAE Journal - August 2008 - Special Products (Page 84) ASHRAE Journal - August 2008 - Classified Advertising (Page 85) ASHRAE Journal - August 2008 - Classified Advertising (Page 86) ASHRAE Journal - August 2008 - Classified Advertising (Page 87) ASHRAE Journal - August 2008 - Advertising Index (Page 88) ASHRAE Journal - August 2008 - Advertising Index (Page Cover3) ASHRAE Journal - August 2008 - Advertising Index (Page Cover4)
For optimal viewing of this digital publication, please enable JavaScript and then refresh the page. If you would like to try to load the digital publication without using Flash Player detection, please click here.