Ashrae Journal - November 2008 - (Page 16) 5 a.m. to 11 a.m. and then begins to drop again at 5 p.m. Server power consumption remains relatively high as server load decreases. In idle mode, most servers consume between 70% and 85% of full operational power. Consequently, a facility operating at just 20% capacity may use 80% of the energy as the same facility operating at 100% capacity. Server processors have power management features built-in that can reduce power when the processor is idle. Too often these features are disabled because of concerns regarding response time. However, this decision may need reevalu- www.info.hotims.com/16019-21 ation in light of the significant savings this technology can enable. In the data center model, it is assumed that idle power draw is 80% of the peak power draw without power management, and reduces to 45% of peak power draw as power management is enabled. With this scenario, power management can save an additional 86 kW or 8% of the unoptimized data center load. 4. Blade servers. Many organizations have implemented blade servers to meet processing requirements and improve server management. While the move to blade servers is typically not driven by energy considerations, they can play a role in energy consumption. Blade servers consume about 10% less power than equivalent rack mount servers because multiple servers share common power supplies, cooling fans, and other components. In the data center model, there is a 1% reduction in total energy consumption when 20% of rack-based servers are replaced with blade servers. More importantly, blades facilitate the move to a high-density data center architecture, which can significantly reduce energy consumption. (See Strategy 9 on High Density Supplemental Cooling.) 5. S erver v irtualization. As server technologies are optimized, virtualization is increasingly being deployed to increase server utilization and reduce the number of servers required. In the data center model, it is assumed that 25% of servers are virtualized with eight nonvirtualized physical servers being replaced by one virtualized physical server. We also assume that the applications being virtualized were residing in single-processor and two-processor servers and the virtualized applications are hosted on servers with at least two processors. Implementing virtualization provides an incremental 8% reduction in total data center power draw for the 5,000 ft2 (465 m2) facility used as the data center model. 6. Cooling best practices. Most data centers have implemented some best practices, such as the hot-aisle/cold-aisle rack arrangement. Potential exists in sealNovember 2008 16 ASHRAE Journal http://www.est-aegis.com/aj2 http://www.est-aegis.com/aj2 http://www.info.hotims.com/16019-21
Table of Contents Feed for the Digital Edition of Ashrae Journal - November 2008 Ashrae Journal - November 2008 Contents Commentary Industry News Meetings and Shows Feature Articles Reducing Data Center Energy Consumption Building Sciences Feature Articles Sustainable Nature Center Emerging Technologies Special Products Washington Report Special Supplement: BACnet® Today BACnet® Goes Green Seeing the Light with BACnet® BACnet® on Campus BACnet® for Net Zero Analyzing BACnet® BACnet® at Xerox Campus BACnet® in Europe BACnet® for Green Library BACnet® at the University of Minnesota: Flexibility, Interoperability InfoCenter Product Showplace Classified Advertising Advertising Index Ashrae Journal - November 2008 Ashrae Journal - November 2008 - Ashrae Journal - November 2008 (Page Cover1) Ashrae Journal - November 2008 - Ashrae Journal - November 2008 (Page Cover2) Ashrae Journal - November 2008 - Ashrae Journal - November 2008 (Page 1) Ashrae Journal - November 2008 - Ashrae Journal - November 2008 (Page 2) Ashrae Journal - November 2008 - Contents (Page 3) Ashrae Journal - November 2008 - Contents (Page 4) Ashrae Journal - November 2008 - Commentary (Page 5) Ashrae Journal - November 2008 - Commentary (Page 6) Ashrae Journal - November 2008 - Industry News (Page 7) Ashrae Journal - November 2008 - Industry News (Page 8) Ashrae Journal - November 2008 - Industry News (Page 9) Ashrae Journal - November 2008 - Industry News (Page 10) Ashrae Journal - November 2008 - Industry News (Page 11) Ashrae Journal - November 2008 - Meetings and Shows (Page 12) Ashrae Journal - November 2008 - Meetings and Shows (Page 13) Ashrae Journal - November 2008 - Reducing Data Center Energy Consumption (Page 14) Ashrae Journal - November 2008 - Reducing Data Center Energy Consumption (Page 15) Ashrae Journal - November 2008 - Reducing Data Center Energy Consumption (Page 16) Ashrae Journal - November 2008 - Reducing Data Center Energy Consumption (Page 17) Ashrae Journal - November 2008 - Reducing Data Center Energy Consumption (Page 18) Ashrae Journal - November 2008 - Reducing Data Center Energy Consumption (Page 19) Ashrae Journal - November 2008 - Reducing Data Center Energy Consumption (Page 20) Ashrae Journal - November 2008 - Reducing Data Center Energy Consumption (Page 21) Ashrae Journal - November 2008 - Reducing Data Center Energy Consumption (Page 22) Ashrae Journal - November 2008 - Reducing Data Center Energy Consumption (Page 23) Ashrae Journal - November 2008 - Reducing Data Center Energy Consumption (Page 24) Ashrae Journal - November 2008 - Reducing Data Center Energy Consumption (Page 25) Ashrae Journal - November 2008 - Reducing Data Center Energy Consumption (Page 26) Ashrae Journal - November 2008 - Reducing Data Center Energy Consumption (Page 27) Ashrae Journal - November 2008 - Building Sciences (Page 28) Ashrae Journal - November 2008 - Building Sciences (Page 29) Ashrae Journal - November 2008 - Building Sciences (Page 30) Ashrae Journal - November 2008 - Building Sciences (Page 31) Ashrae Journal - November 2008 - Building Sciences (Page 32) Ashrae Journal - November 2008 - Building Sciences (Page 32a) Ashrae Journal - November 2008 - Building Sciences (Page 32b) Ashrae Journal - November 2008 - Building Sciences (Page 32c) Ashrae Journal - November 2008 - Building Sciences (Page 32d) Ashrae Journal - November 2008 - Building Sciences (Page 33) Ashrae Journal - November 2008 - Building Sciences (Page 34) Ashrae Journal - November 2008 - Building Sciences (Page 35) Ashrae Journal - November 2008 - Building Sciences (Page 36) Ashrae Journal - November 2008 - Building Sciences (Page 37) Ashrae Journal - November 2008 - Sustainable Nature Center (Page 38) Ashrae Journal - November 2008 - Sustainable Nature Center (Page 39) Ashrae Journal - November 2008 - Sustainable Nature Center (Page 40) Ashrae Journal - November 2008 - Sustainable Nature Center (Page 41) Ashrae Journal - November 2008 - Emerging Technologies (Page 42) Ashrae Journal - November 2008 - Emerging Technologies (Page 43) Ashrae Journal - November 2008 - Emerging Technologies (Page 44) Ashrae Journal - November 2008 - Emerging Technologies (Page 45) Ashrae Journal - November 2008 - Emerging Technologies (Page 46) Ashrae Journal - November 2008 - Emerging Technologies (Page 47) Ashrae Journal - November 2008 - Emerging Technologies (Page 48) Ashrae Journal - November 2008 - Emerging Technologies (Page BCover1) Ashrae Journal - November 2008 - Emerging Technologies (Page BCover2) Ashrae Journal - November 2008 - Emerging Technologies (Page B3) Ashrae Journal - November 2008 - BACnet® Goes Green (Page B4) Ashrae Journal - November 2008 - BACnet® Goes Green (Page B5) Ashrae Journal - November 2008 - BACnet® Goes Green (Page B6) Ashrae Journal - November 2008 - BACnet® Goes Green (Page B7) Ashrae Journal - November 2008 - BACnet® Goes Green (Page B8) Ashrae Journal - November 2008 - BACnet® Goes Green (Page B9) Ashrae Journal - November 2008 - Seeing the Light with BACnet® (Page B10) Ashrae Journal - November 2008 - Seeing the Light with BACnet® (Page B11) Ashrae Journal - November 2008 - Seeing the Light with BACnet® (Page B12) Ashrae Journal - November 2008 - Seeing the Light with BACnet® (Page B13) Ashrae Journal - November 2008 - BACnet® on Campus (Page B14) Ashrae Journal - November 2008 - BACnet® on Campus (Page B15) Ashrae Journal - November 2008 - BACnet® on Campus (Page B16) Ashrae Journal - November 2008 - BACnet® on Campus (Page B17) Ashrae Journal - November 2008 - BACnet® on Campus (Page B18) Ashrae Journal - November 2008 - BACnet® on Campus (Page B19) Ashrae Journal - November 2008 - BACnet® for Net Zero (Page B20) Ashrae Journal - November 2008 - BACnet® for Net Zero (Page B21) Ashrae Journal - November 2008 - BACnet® for Net Zero (Page B22) Ashrae Journal - November 2008 - BACnet® for Net Zero (Page B23) Ashrae Journal - November 2008 - Analyzing BACnet® (Page B24) Ashrae Journal - November 2008 - Analyzing BACnet® (Page B25) Ashrae Journal - November 2008 - Analyzing BACnet® (Page B26) Ashrae Journal - November 2008 - Analyzing BACnet® (Page B27) Ashrae Journal - November 2008 - Analyzing BACnet® (Page B28) Ashrae Journal - November 2008 - Analyzing BACnet® (Page B29) Ashrae Journal - November 2008 - BACnet® at Xerox Campus (Page B30) Ashrae Journal - November 2008 - BACnet® at Xerox Campus (Page B31) Ashrae Journal - November 2008 - BACnet® at Xerox Campus (Page B32) Ashrae Journal - November 2008 - BACnet® at Xerox Campus (Page B33) Ashrae Journal - November 2008 - BACnet® in Europe (Page B34) Ashrae Journal - November 2008 - BACnet® in Europe (Page B35) Ashrae Journal - November 2008 - BACnet® in Europe (Page B36) Ashrae Journal - November 2008 - BACnet® for Green Library (Page B37) Ashrae Journal - November 2008 - BACnet® for Green Library (Page B38) Ashrae Journal - November 2008 - BACnet® for Green Library (Page B39) Ashrae Journal - November 2008 - BACnet® for Green Library (Page B40) Ashrae Journal - November 2008 - BACnet® for Green Library (Page B41) Ashrae Journal - November 2008 - BACnet® at the University of Minnesota: Flexibility, Interoperability (Page B42) Ashrae Journal - November 2008 - BACnet® at the University of Minnesota: Flexibility, Interoperability (Page B43) Ashrae Journal - November 2008 - BACnet® at the University of Minnesota: Flexibility, Interoperability (Page B44) Ashrae Journal - November 2008 - Special Products (Page 49) Ashrae Journal - November 2008 - Washington Report (Page 50) Ashrae Journal - November 2008 - Washington Report (Page 51) Ashrae Journal - November 2008 - Washington Report (Page 52) Ashrae Journal - November 2008 - Washington Report (Page 53) Ashrae Journal - November 2008 - InfoCenter (Page 54) Ashrae Journal - November 2008 - InfoCenter (Page 55) Ashrae Journal - November 2008 - InfoCenter (Page 56) Ashrae Journal - November 2008 - InfoCenter (Page 57) Ashrae Journal - November 2008 - InfoCenter (Page 58) Ashrae Journal - November 2008 - InfoCenter (Page 59) Ashrae Journal - November 2008 - InfoCenter (Page 60) Ashrae Journal - November 2008 - InfoCenter (Page 61) Ashrae Journal - November 2008 - Product Showplace (Page 62) Ashrae Journal - November 2008 - Classified Advertising (Page 63) Ashrae Journal - November 2008 - Classified Advertising (Page 64) Ashrae Journal - November 2008 - Classified Advertising (Page 65) Ashrae Journal - November 2008 - Classified Advertising (Page 66) Ashrae Journal - November 2008 - Classified Advertising (Page 67) Ashrae Journal - November 2008 - Advertising Index (Page 68) Ashrae Journal - November 2008 - Advertising Index (Page Cover3) Ashrae Journal - November 2008 - Advertising Index (Page Cover4)
For optimal viewing of this digital publication, please enable JavaScript and then refresh the page. If you would like to try to load the digital publication without using Flash Player detection, please click here.