DATA CENTERS
disaster recovery plans, commissioning,
and maintenance practices.

Redundancy & Energy Efficiency
In addition to redundancy, there are a
number of strategies regarding whether
the redundant equipment is:
• Connected and running;
• Connected but not running; and
• Not connected but on the premises
(i.e., ready for a cold swap out).
Historically, the data center industry
tends to minimize risk and, therefore,
picked the most conservative of redundancy strategy (i.e., connected and
running). However, with an increased
focus on energy consumption, these
strategies are being revisited by some.
This is particularly true on the electrical
side since this is where the concurrent
operation of parallel paths results in the
largest energy inefficiencies.

Data Center Zoning
Another alternate approach to the
overall data center tiers from the Uptime Institute and the subsystem tiers
described in TIA-942 is to consider splitting the data center’s computer rooms
(also called raised floor area or white
space) into multiple zones and then to
adopt different redundancy strategies per
zone. Dividing the computer room into
many zones facilitates the planning and/
or implementation of various cooling
strategies (e.g., airflow pattern, cooling
source, etc.).
Figure 2 shows a simple zoning pattern, and Table 2 is an example of how
the zones from Figure 2 could be designed with variable criteria including
varying tier levels and provisions for
future tier level upgrades. This zoned
variable criteria approach also ties into
treating cooling systems more like a
service as described in the November
2012 column.

Conclusion
Data centers may require redundant
power and/or redundant cooling depending on the software applications.
Additional redundancy considerations
may apply to other building systems or
124

ASHRAE Journal

the applications themselves. In other
cases, very little to even no redundancy
is required.
The reliability of systems that are
made up of multiple components can
be increased through the addition of
redundant parallel components (eliminate any single points of failure), but
the right balance and tradeoffs need to
be determined with other considerations
(e.g., capital expenditure, energy efficiency, etc.).
Various industry redundancy topologies (tiers) have been defined to help
quantify and compare data center resiliencies. Alternate strategies including
varying the redundancy levels through
zoning your data center computer room
space and applying different tier levels
per zone could yield better results (energy efficiency, total cost of ownership,
etc.) than a single topology approach.
A zoned strategy can also create greater
flexibility in future changes of the
infrastructure to better align with the
rapid change occurring on the software
applications. A more holistic approach
based on the real needs of the software
applications can ensure a better balance of costs, efficiency, schedule, and
availability.

Bibliography
Institute of Electrical and Electronics
Engineers. 1991. IEEE Recommended
Practice for the Design of Reliable

Z1

Z2

Z3
Figure 2: Simple data center computer
room zoning.
Industrial and Commercial Power Systems/Standard 493-1990 (IEEE Gold
Book).
Beaty, D.L. 2005. “Reliability engineering for datacom cooling systems.”
2005 ASHRAE Transactions (111):1.
Telecommunications Industry Association. 2005. ANSI/TIA-942 – Telecommunications Infrastructure Standard for
Data Centers. Arlington: Telecommunications Industry Association.
Uptime Institute. Uptime Tier Ratings.
http://uptimeinstitute.com.
Donald L. Beaty, P.E., is president of
DLB Associates Consulting Engineers,
in Eatontown, N.J. He is publications
chair of ASHRAE TC 9.9.

Topic

Zone 1

Zone 2

Zone 3

Localized Cooling

None

Rear-Door

Row-Based

Allowable Intake Class

A4

A1

A3

Air

Air & Liquid

Liquid

IT Airflow Configuration

F-R

F-R

F-t

Air Distribution

VUF

VUF

VOH

Cold Aisle Containment

No

Yes

No

Tier

II

IV

III

Tier Upgradable

Yes

No

Yes

Cooling Source

Table 2: Variable criteria per zone.
ashrae.org

July 2013



ASHRAE Journal - July 2013

Table of Contents for the Digital Edition of ASHRAE Journal - July 2013

Contents
Commentary
Industry News
Letters
Meetings and Shows
Feature Articles
Sound Advice: Acoustical Specifications for Air Terminals & Air Outlets
Energy Codes and Standards: Part 1: Prescriptive vs. Performance Compliance
Technology Award Case Studies:
Big Plant in a Small Space
Hospital Quality Control
Standing Columns
Building Sciences
Advertising Section
Sustainable Products Capabilities
Refrigeration Applications
Data Centers
IAQ Applications
Energy Modeling
Products
Engineer's Notebook
Classified Advertising
Advertisers Index
ASHRAE Journal - July 2013 - Cover1
ASHRAE Journal - July 2013 - Cover2
ASHRAE Journal - July 2013 - 1
ASHRAE Journal - July 2013 - 2
ASHRAE Journal - July 2013 - Contents
ASHRAE Journal - July 2013 - Commentary
ASHRAE Journal - July 2013 - 5
ASHRAE Journal - July 2013 - Industry News
ASHRAE Journal - July 2013 - 7
ASHRAE Journal - July 2013 - 8
ASHRAE Journal - July 2013 - 9
ASHRAE Journal - July 2013 - 10
ASHRAE Journal - July 2013 - 11
ASHRAE Journal - July 2013 - Letters
ASHRAE Journal - July 2013 - 13
ASHRAE Journal - July 2013 - Meetings and Shows
ASHRAE Journal - July 2013 - 15
ASHRAE Journal - July 2013 - Sound Advice: Acoustical Specifications for Air Terminals & Air Outlets
ASHRAE Journal - July 2013 - 17
ASHRAE Journal - July 2013 - 18
ASHRAE Journal - July 2013 - 19
ASHRAE Journal - July 2013 - 20
ASHRAE Journal - July 2013 - 21
ASHRAE Journal - July 2013 - Energy Codes and Standards: Part 1: Prescriptive vs. Performance Compliance
ASHRAE Journal - July 2013 - 23
ASHRAE Journal - July 2013 - 24
ASHRAE Journal - July 2013 - 25
ASHRAE Journal - July 2013 - 26
ASHRAE Journal - July 2013 - 27
ASHRAE Journal - July 2013 - Big Plant in a Small Space
ASHRAE Journal - July 2013 - 29
ASHRAE Journal - July 2013 - 30
ASHRAE Journal - July 2013 - 31
ASHRAE Journal - July 2013 - 32
ASHRAE Journal - July 2013 - 33
ASHRAE Journal - July 2013 - Hospital Quality Control
ASHRAE Journal - July 2013 - 35
ASHRAE Journal - July 2013 - 36
ASHRAE Journal - July 2013 - 37
ASHRAE Journal - July 2013 - 38
ASHRAE Journal - July 2013 - 39
ASHRAE Journal - July 2013 - Building Sciences
ASHRAE Journal - July 2013 - 41
ASHRAE Journal - July 2013 - 42
ASHRAE Journal - July 2013 - 43
ASHRAE Journal - July 2013 - 44
ASHRAE Journal - July 2013 - 45
ASHRAE Journal - July 2013 - 46
ASHRAE Journal - July 2013 - Sustainable Products Capabilities
ASHRAE Journal - July 2013 - 48
ASHRAE Journal - July 2013 - 49
ASHRAE Journal - July 2013 - 50
ASHRAE Journal - July 2013 - 51
ASHRAE Journal - July 2013 - 52
ASHRAE Journal - July 2013 - 53
ASHRAE Journal - July 2013 - 54
ASHRAE Journal - July 2013 - 55
ASHRAE Journal - July 2013 - 56
ASHRAE Journal - July 2013 - 57
ASHRAE Journal - July 2013 - 58
ASHRAE Journal - July 2013 - 59
ASHRAE Journal - July 2013 - 60
ASHRAE Journal - July 2013 - 61
ASHRAE Journal - July 2013 - 62
ASHRAE Journal - July 2013 - 63
ASHRAE Journal - July 2013 - 64
ASHRAE Journal - July 2013 - 65
ASHRAE Journal - July 2013 - 66
ASHRAE Journal - July 2013 - 67
ASHRAE Journal - July 2013 - 68
ASHRAE Journal - July 2013 - 69
ASHRAE Journal - July 2013 - 70
ASHRAE Journal - July 2013 - 71
ASHRAE Journal - July 2013 - 72
ASHRAE Journal - July 2013 - 73
ASHRAE Journal - July 2013 - 74
ASHRAE Journal - July 2013 - 75
ASHRAE Journal - July 2013 - 76
ASHRAE Journal - July 2013 - 77
ASHRAE Journal - July 2013 - 78
ASHRAE Journal - July 2013 - 79
ASHRAE Journal - July 2013 - 80
ASHRAE Journal - July 2013 - 81
ASHRAE Journal - July 2013 - 82
ASHRAE Journal - July 2013 - 83
ASHRAE Journal - July 2013 - 84
ASHRAE Journal - July 2013 - 85
ASHRAE Journal - July 2013 - 86
ASHRAE Journal - July 2013 - 87
ASHRAE Journal - July 2013 - 88
ASHRAE Journal - July 2013 - 89
ASHRAE Journal - July 2013 - 90
ASHRAE Journal - July 2013 - 91
ASHRAE Journal - July 2013 - 92
ASHRAE Journal - July 2013 - 93
ASHRAE Journal - July 2013 - 94
ASHRAE Journal - July 2013 - 95
ASHRAE Journal - July 2013 - 96
ASHRAE Journal - July 2013 - 97
ASHRAE Journal - July 2013 - 98
ASHRAE Journal - July 2013 - 99
ASHRAE Journal - July 2013 - 100
ASHRAE Journal - July 2013 - 101
ASHRAE Journal - July 2013 - 102
ASHRAE Journal - July 2013 - 103
ASHRAE Journal - July 2013 - 104
ASHRAE Journal - July 2013 - 105
ASHRAE Journal - July 2013 - 106
ASHRAE Journal - July 2013 - 107
ASHRAE Journal - July 2013 - 108
ASHRAE Journal - July 2013 - 109
ASHRAE Journal - July 2013 - 110
ASHRAE Journal - July 2013 - 111
ASHRAE Journal - July 2013 - 112
ASHRAE Journal - July 2013 - 113
ASHRAE Journal - July 2013 - 114
ASHRAE Journal - July 2013 - 115
ASHRAE Journal - July 2013 - 116
ASHRAE Journal - July 2013 - 117
ASHRAE Journal - July 2013 - 118
ASHRAE Journal - July 2013 - 119
ASHRAE Journal - July 2013 - 120
ASHRAE Journal - July 2013 - Refrigeration Applications
ASHRAE Journal - July 2013 - Data Centers
ASHRAE Journal - July 2013 - 123
ASHRAE Journal - July 2013 - 124
ASHRAE Journal - July 2013 - 125
ASHRAE Journal - July 2013 - IAQ Applications
ASHRAE Journal - July 2013 - 127
ASHRAE Journal - July 2013 - 128
ASHRAE Journal - July 2013 - 129
ASHRAE Journal - July 2013 - Energy Modeling
ASHRAE Journal - July 2013 - 131
ASHRAE Journal - July 2013 - Products
ASHRAE Journal - July 2013 - 133
ASHRAE Journal - July 2013 - Engineer's Notebook
ASHRAE Journal - July 2013 - Classified Advertising
ASHRAE Journal - July 2013 - Advertisers Index
ASHRAE Journal - July 2013 - Cover3
ASHRAE Journal - July 2013 - Cover4
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_MCDEBX
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_WNYSQY
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_XATVOD
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_FJSHSS
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_CCBZDS
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_XDEFVG
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_amca_2023november_v2
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_amca_2023november
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_VHGNBL
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_WPKBNJ
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_UUVCDE
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_RTGDEW
https://www.nxtbook.com/nxtbooks/ashrae/ashraemexico_2023
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_LKRFXS
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_AZSOFG
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_ERCDBH
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_QWDFRV
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_JHGVDF
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_OPUYHG
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_SREIBM
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_LRTGLK
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_OKRFGH
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_amca_2022november_v2
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_amca_2022november
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_TZSERA
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_LVRUIX
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_RPTVYZ
https://www.nxtbook.com/nxtbooks/ashrae/mini_pub_catalog
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_XIYTGD
https://www.nxtbook.com/nxtbooks/ashrae/ashraemexico_2022
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_RFGDOB
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_PABXNU
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_REMKLS
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_PICVBT
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_AOYTVW
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_JQOPLS
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_IOYTBC
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_SGAJJF
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_IGHYER
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_PDRKLS
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_amca_2021november
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_amca_2021november_v2
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_XCODFR
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_QSLFGO
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_ILKVNM
https://www.nxtbook.com/nxtbooks/ashrae/ashraemexico_2021
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_OPDJKD
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_VJKSRY
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_SDHUTC
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_JPPKRR
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_SDLTTH
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_CKLLES
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_SLDOX
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_HJETUK
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_OLUHGE
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_amca_2020october
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_amca_2020october_v2
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_ZERDGH
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_QVMNEO
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_RTPOKE
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_BBATRE
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_STUBMW
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_TPEMPE
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_JNMKDS
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_FBTTPA
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_WQMMNE
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_TVBRYN
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_showguide2020
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_KTUZMA
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_ABEDGD
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_201910
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_201909
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_amca_2019septmeber_v2
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_amca_2019september
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_201908
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_201907
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_201906
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_201905
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_201904
https://www.nxtbook.com/nxtbooks/ashrae/meetingplanner_2019april
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_201903
https://www.nxtbook.com/nxtbooks/ashrae/meetingplanner_2019march
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_201902
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_201901
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_showguide2019
https://www.nxtbook.com/nxtbooks/ashrae/meetingplanner_2018december
https://www.nxtbook.com/nxtbooks/ashrae/meetingplanner_2018november
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_amca_2018fall_v2
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_amca_2018fall
https://www.nxtbook.com/nxtbooks/ashrae/meetingplanner_2018october
https://www.nxtbook.com/nxtbooks/ashrae/ashraemexico_2018
https://www.nxtbook.com/nxtbooks/ashrae/meetingplanner_201810
https://www.nxtbook.com/nxtbooks/ashrae/ashraeinsights_201806
https://www.nxtbook.com/nxtbooks/ashrae/meetingplanner_201805
https://www.nxtbook.com/nxtbooks/ashrae/meetingplanner_201804
https://www.nxtbook.com/nxtbooks/ashrae/meetingplanner_201803
https://www.nxtbook.com/nxtbooks/ashrae/meetingplanner_201712
https://www.nxtbook.com/nxtbooks/ashrae/meetingplanner_201711
https://www.nxtbook.com/nxtbooks/ashrae/meetingplanner_201710
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_amca_2017fall_v2
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_amca_2017fall
https://www.nxtbook.com/nxtbooks/ashrae/meetingplanner_201709
https://www.nxtbook.com/nxtbooks/ashrae/meetingplanner_201705
https://www.nxtbook.com/nxtbooks/ashrae/ashrae_meetinginsert_201610
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_amca_2016fall_v2
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_amca_2016fall
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_acrexindia
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_amca_2015summer_v2
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_amca_2015summer
https://www.nxtbook.com/nxtbooks/amca/2014summer2
https://www.nxtbook.com/nxtbooks/amca/2014summer
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_acma_2014summer
https://www.nxtbook.com/nxtbooks/ashrae/meetingplanner_201311
https://www.nxtbook.com/nxtbooks/ashrae/meetingplanner_201309
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_acmasupp_2013fall
https://www.nxtbook.com/nxtbooks/ashrae/meetingplanner_201305
https://www.nxtbook.com/nxtbooks/ashrae/meetingplanner_201303
https://www.nxtbook.com/nxtbooks/ashrae/pubcatalog_2013winter
https://www.nxtbook.com/nxtbooks/ashrae/meetingplanner_201211
https://www.nxtbook.com/nxtbooks/ashrae/achr_expo_mexico2012
https://www.nxtbook.com/nxtbooks/ashrae/meetingplanner_201209
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_201208_v3
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_201208_v2
https://www.nxtbook.com/nxtbooks/ashrae/pubcatalog_2012summer
https://www.nxtbook.com/nxtbooks/ashrae/meetingplanner_201205
https://www.nxtbook.com/nxtbooks/ashrae/meetingplanner_201203
https://www.nxtbook.com/nxtbooks/ashrae/pubcatalog_2012winter
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_201111_v2
https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_201109_v2
https://www.nxtbook.com/nxtbooks/ashrae/pubcatalog_2011summer
https://www.nxtbook.com/nxtbooks/ashrae/meetingplanner_201105
https://www.nxtbook.com/nxtbooks/ashrae/meetingplanner_201103
https://www.nxtbookmedia.com