Compressed Air Best Practices - October 2008 - (Page 27) Focu ndustry A TOMOTIV RAN Focus Industry AUTOMOT VE TRANSIT us | 10/08 | IN CANADA FOR COACH INDUSTRIES Pinpointing Problems Manitoba Hydro installed data loggers at critical points in the compressed air system to monitor pressure, temperature, current and dew point. Readings recorded by the loggers showed exactly what was happening throughout the system. Pressure drops were caused mainly by incorrect timer settings and manual operation of the compressors. Another factor was heat build-up in rooms housing the compressors. Temperatures would soar as high as 50 °C, forcing the compressors to shut down. In addition, leak tests with an ultrasonic leak detector identified air leakage serious enough to keep a 125-hp (horsepower) compressor running c continuously. Recommendat Recommendations ommendat The audit recommended the following solutions: ommended p upgrading ventil ventilation in the tila latio compressor rooms to preven r r oms prevent overheating of the compressors g he installin heat recovery systems installing ecovery in the compressor rooms so th c sor that hot exhaust air could be used h se to warm parts of the plant during the winter months th nths installing an 8,20 talling 8,200-gallon receiver li 20 2 k f c tank and flow controller to cushion co compre the compressors from large air events, and keep the minimum e ents, an en a mber mbe number of compressors on line www.airbestpractices.com p p 27 http://www.epiflow.com http://www.epiflow.com http://www.airbestpractices.com