Best Practice Guide for Warehouses 2008 - (Page 12) WAREHOUSE Storage BUILDINGS W-WA1.0 Warehouse Area: occupancy sensing • individual luminaire control Control Needs Automatically turn lights on and off based on occupancy; detect forklift operation Individual luminaire control Night lights on all of the time Night lights operate during power outage Solution PIR occupancy sensors (HB series) Application Description Space Use: Dimensions: Ceiling Height: Windows: Skylights: Bulk & Rack Storage Bulk Storage 50’ x 50’ Rack Storage 12’ x 160’ Bulk & Rack Storage 35’ None None Line voltage sensor mounted to each luminaire Night lights are not controlled Power from emergency panel Lighting Pendant-mounted turret industrial fluorescent luminaires with 15% uplight, 8’ long, using six T8 fluorescent lamps and tandem-wired two-lamp 277-volt electronic ballasts. Luminaires are mounted 32’ above finish floor. Bulk & Rack Bulk Storage Partial Lighting Plan Rack Storage Partial Lighting Plan Design Solution Description Each luminaire is individually controlled using a 277-volt HB350-B PIR occupancy sensor mounted to the end of the luminaire. Sensors in the Bulk Storage area use an HBL4 360° lens; sensors in the Rack Storage area use an HBL1 aisleway lens with a long and narrow field of view to detect forklifts in time to turn lighting on. Night light luminaires are not controlled and remain on at night and during a power outage. Code Compliance Guide ASHRAE IECC TITLE 24 1999 2003 2005 2001 2004S 2004 2006 12 Watt Stopper/Legrand W-WA1.0 0508