Best Practice Guide for Warehouses 2008 - (Page 50) WAREHOUSE Receiving BUILDINGS W-SR1.0 Shipping & Receiving: occupancy sensing Control Needs Automatically turn lights on and off based on occupancy; detect forklift operation Individual luminaire control Night lights on all of the time Night lights operate during power outage Solution PIR occupancy sensors (HB series) Line voltage sensor mounted to each luminaire Night lights are not controlled Power from emergency panel Application Description Space Use: Dimensions: Ceiling Height: Windows: Skylights: Shipping and receiving 50’ x 150’ 20’ None None Lighting Pendant-mounted turret industrial fluorescent luminaires with 15% uplight, 8’ long, using six T8 fluorescent lamps and tandem-wired two-lamp 277-volt electronic ballasts. Luminaires are mounted 16’ above finish floor. Shipping & Receiving Plan Shipping & LEGEND LEGEND Design Solution Description Each luminaire is individually controlled using a line voltage HB350-B PIR occupancy sensor mounted to the end of the luminaire. The sensor has an HBL3 lens with a 360° field of view; sensor spacing provides overlapping coverage. Night light luminaires are not controlled and remain on at night and during a power outage. Code Compliance Guide ASHRAE IECC TITLE 24 1999 2003 2005 2001 2004S 2004 2006 50 Watt Stopper/Legrand W-SR1.0 0508