Best Practice Guide for Warehouses 2008 - (Page 70) WAREHOUSE Room BUILDINGS W-CR2.0 Small Conference Room: occupancy sensing • manual on Control Needs Manual lighting control with automatic off based on occupancy; dual controls for bi-level switching Solution Dual technology wall switch occupancy sensor; tandemwired ballasts and dual relay sensor (DW series) Application Description Space Use: Dimensions: Ceiling Height: Windows: Skylights: Meetings, presentations, group projects 10’ x 10’ 10’ Along one wall providing view to exterior None Conference Lighting Pendant-mounted indirect/direct 4’ luminaires, using three T8 lamps and two-lamp tandem-wired electronic ballasts. Conference Room Lighting Plan LEGEND LEGEND Design Solution Description A DW-200 dual technology wall switch occupancy sensor is used to automatically turn lights off when the room is unoccupied. Manual on and off control is provided by two buttons, each controlling an independent relay. The dual relays enable simple and effective bi-level switching. Code Compliance Guide ASHRAE IECC TITLE 24 1999 2003 2005 2001 2004S 2004 2006 70 Watt Stopper/Legrand W-CR2.0 0508