YES 45 TU/FT Thermal Storefront System YES 45 TU WIND LOAD CHARTS DEFLECTION CRITERIA: AAMA TIR-A11 - L/175 for ≤ 13'-6 " span or L/240 + 1/4 " (6.4mm) - FOR SPANS GREATER THAN 13'-6 " (4.1m) BUT LESS THAN 40'-0 " (12.2m) CODES AND SPECIFICATIONS MAY VARY, NO SINGLE LITE OF GLASS SHALL DEFLECT MORE THAN 3/4 " (19.1mm) ALONG SUPPORTED EDGE. ALLOWABLE WIND LOAD CHARTS YKK AP tested standard. Contact YKK AP for more information. These charts include unbraced length analysis and are based off at least one horizontal being placed at the midpoint of the span. For other applications, please contact YKK AP engineers at 1-866-955-2732. BE9-2551/ BE9-2552 V E R T I C A L H E I G H T (FT) 234 567 VERTICAL SPACING (FT) BE9-2555 V E R T I C A L H E I G H T (FT) 234 567 VERTICAL SPACING (FT) Page-10 10 11 12 13 14 15 6 7 8 9 V E R T I C A L A B C D Ixx=3.000 in4 (124.9 cm )4 Ixx=4.990 in4 (207.7cm)4 H E I G H T (FT) 234 567 VERTICAL SPACING (FT) 02-1003-14 | Effective Date: January 10. 2022 10 11 12 13 14 15 7 8 9 10 11 12 13 14 6 7 8 9 A B C D Ixx=2.995 in4 (124.65 cm )4 Ixx=2.998 in4 (cm)4 124.78 V E R T I C A L H E I G H T A=15 PSF (720 Pa) B=20 PSF (960 Pa) C=30 PSF (1440 Pa) D=40 PSF (1920 Pa) (FT) 234 567 VERTICAL SPACING (FT) BE9-2561/ BE9-2552 10 11 12 13 14 6 7 8 9 A B C D BE9-2553/ BE9-2552 A B C D