YES 45 FT Thermal Storefront System YES 45 FT WIND LOAD CHARTS DEFLECTION CRITERIA: AAMA TIR-A11 - L/175 FOR ≤ 13'-6 " SPAN OR L/240 + 1/4 " (6.4mm) - FOR SPANS GREATER THAN 13'-6 " (4.1m) BUT LESS THAN 40'-0 " (12.2m) CODES AND SPECIFICATIONS MAY VARY, NO SINGLE LITE OF GLASS SHALL DEFLECT MORE THAN 3/4 " (19.1mm) ALONG SUPPORTED EDGE. ALLOWABLE WIND LOAD STRESS YKK AP tested standard. Contact YKK AP for more information. These charts include unbraced length analysis and are based off at least one horizontal being placed at the midpoint of the span. For other applications, please contact YKK AP engineers at 1-866-955-2732. BE9-1503/ BE9-2605 V E R T I C A L H E I G H T ( FT) 234567 VERTICALSPACING (FT) 10 11 12 13 14 15 6 7 8 9 V E R T I C A L A B C D A=15 PSF (720 Pa) B=20 PSF (960 Pa) C=30 PSF (1440 Pa) D=40 PSF (1920 Pa) BE9-1518/ BE9-1519 V E R T I C A L H E I G H T ( FT) 234567 VERTICALSPACING (FT) Effective Date: Aug 23, 2024 | 02-1003-18 10 11 12 13 14 15 7 8 9 V E R T I C A L A B C D Ixx=3.364 in4 (140.02 cm )4 Ixx=5.531 in4 (230.22 cm )4 H E I G H T ( FT) 2 34567 VERTICALSPACING (FT) Page-35 10 11 12 13 14 15 16 17 8 9 Ixx=3.162 in4 (131.61 cm )4 Ixx=3.425 in4 (142.56 cm )4 H E I G H T ( FT) 234567 VERTICALSPACING (FT) 10 11 12 13 14 15 6 7 8 9 BE9-1507 A B C D BE9-1515/ BE9-2605 A B C D