PASS & SEYMOUR / GFCIs & AFCIs GFCIs radiant® North American Tamper-Resistant and Weather-Resistant Self-Test GFCI Receptacles with SafeLock® Protection 2 Pole, 3 Wire Grounding 15 & 20A, 125VAC 1.25 " 1.03 " 2.70 " 4.20 " 1.03 " 2.70 " 4.20 " 1.25 " 1.73 " 1.73 " 1597TRWRNAW 2097TRWRNAW Features * Part of the radiant® collection of wiring devices, wall plates and home systems. * Conducts an automatic test every three seconds, ensuring it's always ready to protect. If the device fails the test, the indicator light flashes to signal that the GFCI should be replaced. It also has our proven SafeLock Protection feature: if critical components are damaged and protection is lost, power to the receptacle is disconnected. * Auto-Ground clip assures a positive ground to metal box. * Feed-thru wiring configuration allows GFCI to protect downstream receptacles. * Prevents line-load reversal miswire: no power to the face or downstream receptacles if wired incorrectly. * Exceeds UL943 voltage surge requirements. * FSUL Listed (Federal Specification WC596). * Trip indicator light (red LED). * Ground screw has a back wire clamp for easy installation. * RoHS compliant. * Proposition 65 compliant. Specifications * Supply Voltage: 125VAC, 60 Hz * Supply Voltage Range: 102-132 VAC RATING CATALOG NUMBER A 1597TRWRNALA 15 15 15 15 VAC 125 COLOR Ivory NEMA CONFIG. NO. TAMPER-RESISTANT/WEATHER-RESISTANT 15 AMP DUPLEX GFCI 1597TRWRNAI 1597TRWRNAW 1597TRWRNA 125 White Brown 125 125 20 20 20 20 20 125 125 Light Almond Ivory 5-15R 5-15R 5-15R 5-15R TAMPER-RESISTANT/WEATHER-RESISTANT 20 AMP DUPLEX GFCI 2097TRWRNAI 2097TRWRNAW 2097TRWRNABK 2097TRWRNAGRY 2097TRWRNALA 125 White Black 125 Gray 125 Light Almond 5-20R 5-20R 5-20R 5-20R 5-20R UL943 C22.2 No. 144 * * * * * * * * * UL498 C22.2 No. 42 * * * * * * * * * FSUL WC596 * * * * * * * * * * Torque terminal screws to 14-16 inchpounds. * Side or internal screw-pressure-plate back wire with #10 - #14 AWG solid or stranded copper wire. * Two back wire holes per terminal. * Class A rated GFCI. * Supplied with matching TP26 nylon wall plate. * Tri-drive screws. * GFCIs with Auto-Ground assure a positive ground to metal box. * WR models listed to the WeatherResistant supplement of UL498, meet demanding UL requirements. * Trip Threshold: 5± 1mA * Trip Time: 0.025 sec., nominal per UL Standard * 20 Amp feed-thru capacity 3rd PARTY COMPLIANCE NEMA 5-15R NEMA 5-20R 188 WWW.LEGRAND.US/PASSANDSEYMOUR GFCIs & AFCIshttp://WWW.LEGRAND.US/PASSANDSEYMOUR