RELAY OUTPUT Series 19MR Direct Motor Load of 30 Amps @ 240 VAC Series 19MR controls are the ideal choice where pump up or pump down service is necessary. This control eliminates the need for contactors because it can directly handle motors up to 1 HP at 120 VAC, or motors up to 2 HP at 240 VAC. Use the Bold characters from the chart below to construct a product code. 19MR X Series 19MR * Carbonators * Appliances * Sumps * Low-Water Cutoff * Direct Motor Load Dimensions KEYHOLE & SLOT FOR TWO SIZE 6 MOUNTING SCREWS G L 4 - NEMA 4 120V 4˝ (10.16 cm) H LOAD Mode of Operation Direct Inverse A - 11K C - 11K B - 19K D - 19K Enclosure 0 - None 1 - NEMA 1 X Applications COM/L2 120V 240V 1-7/16˝ 1-7/16˝ (3.7 cm) (3.7 cm) 2-7/8˝ (7.3 cm) 1-1/2˝ (3.8 cm) Wiring WARRICK CONDUCTIVITY SENSORS How to Order Series 19MR 3-1/2˝ (8.9 cm) Primary Voltage Secondary Voltage Temperature Approvals Optional 30 amp @ 240 VAC SPST 30 A at supply voltage (120 or 240 VAC) 1 hp for 120 VAC; 2 hp for 240 VAC 3/16˝ spade lug on probe connections 1/4˝ spade lug on power connections 120 VAC or 240 VAC (+10%/-15%), 50/60 Hz 11.0 VAC, 1.5 mA -40°F to +150°F (-40°C to +65°C) U.L. 508 File # E44426, Vol. 1 Sec. 6 240V COM/L2 Enclosures Output Contact Rating Powered Output Contact Horsepower Range Terminals Caution: 19MR contacts are powered contacts. When power is applied to the 19MR controller, power may be present on relay output connections. Output voltage will be same as input voltage. Series 19MR / p1of1 / 3-APR-14 Visit www.GemsSensors.com for most current information. E-12http://ecatalog.gemssensors.com/ecatalog/warrick-controls/en/gemslink/1=19MR http://www.GemsSensors.com